Chapter 19 Use GuardPLC Controller as an Adapter

2. Set the WriteBuffer display type to Hex. Enter 16#12, 16#34,

16#ab, 16#cd in the WriteBuffer.

3. Set the ReadBuffer type to Decimal.

The ReadBuffer is set to Decimal because RSLogix Guard PLUS!
software displays DINT types in decimal format only.

4. Configure the Force Editor menu in RSLogix Guard PLUS!

software to display all signals for assemblies IN_120 and
OUT_121.

5. Set signals for the IN_120 assembly to values 12345678,

13572468, 98765432.

6. Start forcing to send the new signal values.

7. Verify that RSLogix 5000 software displays the same values in

the ReadBuffer.

8. Verify that the OUT_121 signals show 16#12, 16#34, 16#ab,

16#cd.