1753-ow8 relay output module – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 294

Advertising
background image

294

Publication 1753-UM001C-EN-P - March 2010

Appendix A Specifications

1753-OW8 Relay Output Module

Attribute

1753-OW8

Response Time

10 ms

GuardPLC Ethernet
Interfaces

2 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated switch

Operating voltage

24V DC, -15%…20%, w

ss

15% from a power supply with

protective separation conforming to IEC 61131-2 requirements

Current consumption

0.6 A max (with max load)

Isolation voltage

No isolation between circuits

Wiring category

(1)

category 2 on communication ports, signal ports, and power
ports

Wire size

I/O – 1.5 mm

2

(16 AWG)…0.14 mm

2

(26 AWG) solid or stranded

copper wire rated at 75 °C (167 °F) or greater with 3/64 inch
(1.2 mm) insulation max

Power – 2.5 mm

2

(14 AWG)

…0.34 mm

2

(22 AWG) solid or

stranded copper wire rated at 75 °C (167 °F) or greater with
3/64 inch (1.2 mm) insulation max

Terminal block torque 0.51 Nm (4.5 in-lb)

Fuse (external)

10 A (slow blow)

Battery backup

none

Relay Outputs

Number of outputs

8 normally open contacts

Switching voltage

5V,

250V AC/250V DC

Switching current

UL: 24V DC @ 1 A resistive load, 250V AC @ 6 A general
purpose

TÜV:

up to 240VA (for V AC)

up to 30V DC @ 90 W

up to 70V DC @ 35 W

up to 127V DC @ 30 W

Turn-on time

approx. 30 ms

Turn-off time

approx. 10 ms

Bounce time

approx. 15 ms

Service life,
mechanical

10

6

switching cycles

Service life, electrical

2.5 x 10

5

switching cycles with resisitive full load and

I

e

0.1

switching cycles per second

Environmental Conditions

Temperature,
operating

0...60 °C (32...140 °F)

Temperature, storage

-40...85 °C (-40...185 °F)

Vibration

1 g @ 10…150 Hz

Advertising