Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 324

Advertising
background image

324

Publication 1753-UM001C-EN-P - March 2010

Appendix B System Signal Variables

AI[xx].Error Code

(1)

Read

Error code of analog input channels

0x01

Error in the analog input module

0x02

Limit value underflow/overflow

0x04

A/D converter faulty; measuring values not valid

0x08

Measured value not within safety accuracy

0x10

Measured value overflow

0x20

Channel not in operation

0x40

Address error of both A/D converters

AI[xx].Value

Read

Analog value of each channel [INT] from 0…2000 (0V…10V). The validity depends on
the AI[xx].Error Code.

AI[xx].Used

Write

Configures the channel for operation

0

Channel is not in operation.

1

Channel is operating.

AI[xx].Transmitter Used

Write

Configures the channel for transmitter supply

0

Transmitter supply is not used.

1

Transmitter supply is used.

Transmitter Voltage[01]

Write

Configures switchover of the transmitter supply per group

1

8.2V

2

26.0V

Transmitter.Error Code

Read

Error codes of the transmitter unit

0x0001

Error in the transmitter supply

0x0400

FTZ test 1: temperature threshold exceeded

0x0800

FTZ test 2: temperature threshold exceeded

Transmitter[01].Error Code

Read

Error codes of each transmitter group

0x01

Module error of transmitter supply

0x02

Overcurrent of transmitter supply

0x04

Undervoltage of transmitter supply

0x08

Overvoltage of transmitter supply

AI[xx].Underflow

Read

Underflow AI[xx].Value according to AI[xx].Limit LOW.
The validity depends upon the AI[xx].Error Code.

AI[xx].Overflow

Read

Overflow AI[xx].Value according to AI[xx].Limit HIGH.
The validity depends upon the AI[xx].Error Code.

AI[xx].Limit LOW

Write

Upper limit of voltage range 0-signal AI[xx].Underflow

AI[xx].Limit HIGH

Write

Lower limit of voltage range 0-signal AI[xx].Overflow

(1) xx = affected output channel of the controller or module.

I/O Data

Read/Write

Description