Digital relay output parameters for 1753-ow8, Modules – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 322

Advertising
background image

322

Publication 1753-UM001C-EN-P - March 2010

Appendix B System Signal Variables

Digital Relay Output Parameters for 1753-OW8 Modules

The 1753-OW8 module supports these digital output parameters.

I/O Data

Read/Write

Description

DO.Error Code

Read

Error mask for all digital outputs

0x0001

Module error

0x0002

MEZ test, safety switch 1 failed

0x0004

MEZ test, safety switch 2 failed

0x0008

FTZ test of test pattern failed

0x0010

MEZ test of test of readback channels failed

0x0020

MEZ test, active disconnection failed

0x0040

Error with initialization: relays

0x0080

FTZ test: error of relay voltage

0x0100

FTZ test of chip select (cs) signals failed

0x0400

FTZ test: 1. Temperature threshold exceeded

0x0800

FTZ test: 2. Temperature threshold exceeded

0x1000

MEZ test: status of safety switch 1

0x2000

MEZ test: status of safety switches

0x4000

MEZ test: active disconnection by watchdog failed

DO[xx].Error Code

(1)

Read

Error code of digital output channels

0x01

Error in the digital output module

0x04

Error reading back the digital outputs

0x10

Error reading back relay [x].1 (The channel is permanently
deactivated.)

0x20

Error reading back relay [x].2 (The channel is permanently
deactivated.)

0x80

Channel cannot be activated after deactivation by:

user program

forcing

channel/module failure

DO[xx].Value

Write

Output value for DO channels

0

Output not powered.

1

Output activated.

(1) xx = affected output channel of the controller or module.