Chapter 4 Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Safety-related High-speed Counter Terminals

Counters are connected to these terminals.

Wire the GuardPLC 1200
Controller

The GuardPLC 1200 controller has no LS+ terminal for a safety input
voltage source. Use the L+ supply terminal as the source for safety
input voltage. The four reference terminals, labeled I-, should be used
for the safety input voltage reference. This is a common reference for
all 20 inputs.

Lower Terminal Block

Terminal Number

Designation

Counter Function

Gray Code Function

65

A1

Input A1

bit 0 (LSB)

66

B1

Input B1

bit 1

67

Z1

Input Z1

bit 2 (MSB)

68

L-

Common reference pole

69

A2

Input A2

bit 0 (LSB)

70

B2

Input B2

bit 1

71

Z2

Input Z2

bit 2 (MSB)

72

L-

Common reference pole