Appendix B System Signal Variables

Digital Output Module Variables for GuardPLC 1600/1800
Controllers, 1753-IB20XOB8 Modules, and 1753-OB16 Modules

The GuardPLC 1600 and GuardPLC 1800 controllers, 1753-IB20XOB8
modules, and 1753-OB16 modules support these digital output
parameters.

I/O Data

Read/Write

Description

DO.Error Code

Read

Error mask for all digital outputs

0x0001

Error in digital output range

0x0002

MEZ test of test pattern failed

0x0004

MEZ test, auxiliary supply failed

0x0010

FTZ test of test pattern failed

0x0020

FTZ test of test pattern of the output switch failed.

0x0040

FTZ test of the test pattern of the output switch (disconnection test
of outputs) failed.

DO[xx].Error Code

(1)

Read

Error mask of all digital output channels

0x01

Error in digital output module

0x02

Output switched off due to overload

0x04

Error when reading back the activation of the digital outputs

0x08

Error when reading back the status of the digital outputs

(1) xx = affected output channel of the controller or module.