Publication 1753-UM001C-EN-P - March 2010

279

Communicate with Modbus and Profibus Devices Chapter 22

Profibus DP Slave Protocol

Profibus DP Slave protocol is available only via the GuardPLC 1600
and 1800 controller’s COMM1 port. This connection is two-way
non-safety-related communication from the controller (slave) to the
master device. You cannot program the controller by using this port.

To use the Profibus DP function, signals that you wish to send out the
COMM1 port must be connected to placeholders in the Profibus
DP-protocol Connect Signals dialog box.

Connect the Controller to a Profibus DP Device

L-

L+

L+

COMM3

ASCII

RS-485

24V DC

COMM2

COMM1

GuardPLC Ethernet

10/100 BaseT

PROFIBUS

3

(—)

4

(—)

3

(—)

4

(—)

RS-485

Connection

Signal

Function

1

---

---

2

RP

5V, decoupled with diodes

3

RxD/TxD-A

Receive/Transmit data A

4

CNTR-A

Control Signal A

5

DGND

Data reference potential

6

VP

5V, positive pole of supply voltage

7

---

---

8

RxD/TxD-B

Receive/Transmit data B

9

CNTR-B

Control Signal B

IMPORTANT

The Profibus port is RS-485. You must use an electrical
interface device to connect the controller to an RS-232 device.