Define the signals to exchange between each, Controller connection – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 187

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

187

Configure Peer-to-Peer Communication Chapter 17

on page

157

), ReceiveTMO must be calculated and set manually by

overwriting the default value in the Peer-to-Peer Editor.

For profiles where ProdRate = 0 (Fast & Cleanroom, Fast & Noisy),
ReceiveTMO is:

ReceiveTMO = T

R

– 2 x WDZ(PES

1

) – 2 x WDZ(PES

2

)

For profiles where ProdRate

0, ReceiveTMO is:

ReceiveTMO = [T

R

– 3 x WDZ(PES

1

) – 2 x WDZ(PES

2

)]

÷

2

Calculate the ReceiveTMO with the suitable formula and overwrite the
default value in the Peer-to-Peer Editor.

In first approximation, the ResponseTime can be calculated as:

ResponseTime = ReceiveTMO

÷

2

Overwrite the default value of the ResponseTime with the calculated
value.

Define The Signals to Exchange Between Each Controller
Connection

1. Right-click a resource in the project tree and choose

Peer-to-Peer Editor.

The Peer-to-Peer Editor opens.

2. Click a line number (leftmost column) in the Peer-to-Peer Editor

table.

This selects a controller with which the controller, named in the
headline of the Peer-to-Peer Editor, exchanges data.

TIP

Setting the ResponseTime this way allows the controller to
resend a message, in case of unexpected message loss. For
best network performance, the ReceiveTMO and the
ResponseTime are optimized after the project has been
compiled, loaded and started on the controllers. At that time,
the actual ResponseTimes and the actual cycle times can be
read in the Control Panel.

Advertising