Installation Chapter 2

Back Panel

Use the four brackets on the GuardPLC 1200 controller to mount it
onto a back panel.

If the mounting brackets are not flat before the nuts are tightened, use
additional washers as shims, so the controller does not bend when
you tighten the nuts.

GuardPLC 1600 and GuardPLC 1800 Controllers,
and Distributed I/O

ATTENTION

Do not bend the controller. Bending the controller will damage
it.

PLC

1200

Bottom Brackets

Top Brackets

Use the following to mount the
controller.

Top Brackets

Bottom Brackets

M4 screws (2)

M5 screws (2)

lock washer

lock washer

washers

washers

nut

nut

IMPORTANT

For effective cooling:

mount the device horizontally.

provide a gap of at least 100 mm (3.94 in.) above and below the device and at
least 20 mm (0.79 in.) horizontally between devices.

the wire duct can run in the 100 mm (3.94 in.) of free space above and below
the controller if it is no deeper than 40 mm (1.58 in.). If the depth is greater
than 40 mm (1.58 in.), the devices must be placed on stand-offs that match the
depth of the duct. If stand-offs are not used, you must provide a gap of at least
80 mm (3.15 in.) between the device and the duct.

select a location where air flows freely or use an additional fan.

do not mount the controller or I/O module over a heating device.

do not block the ventilation slots on the side of the device.