Wire the 1753-IF8XOF4 Analog I/O Module

Introduction

The 1753-IF8XOF4 module features 8 safety analog inputs and 4
standard analog outputs.

Safety-related Analog
Inputs

These input values are available.

Voltage Measurement

If an open-circuit fault occurs during voltage measurement,
unpredictable input signals are received on the high resistance inputs.
Values resulting from this fluctuating input voltage are not reliable.
Because the module does not feature circuit monitoring, you must
terminate input channels with a 10 k

Ω

resistor when measuring

voltage. Consider the internal resistance of the source as well.

Current Measurement

To measure current, connect a 500

Ω

external shunt in parallel to the

input. Accuracy of the shunt must be included in accuracy calculations
of the input signal. Terminating resistors are not required for current
measurement with the external shunt connected in parallel.

Topic

Page

Safety-related Analog Inputs

95

Standard Analog Outputs

97

Input Channels

Polarity

Current or Voltage

Range

Safety
Accuracy

8

unipolar

0…+10V

0…2000

2%

0…20 mA / 4…20
mA

0…1000

(1)

0…2000

(2)

(1) With external 250

Ω

shunt.

(2) With external 500

Ω

shunt.