Terminal connections – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 96

Advertising
background image

96

Publication 1753-UM001C-EN-P - March 2010

Chapter 9 Wire the 1753-IF8XOF4 Analog I/O Module

Terminal Connections

Analog cabling should be no more than 300 m (984 ft) in length and
must be shielded, twisted-pair cables for each measurement input.
The shields must be connected at one end.

See the wire size and terminal torques specifications on page

292

.

Analog inputs (AI) are connected to these terminals.

IMPORTANT

Short-circuit unused input channels to the reference pole by
connecting wire jumpers.

Terminal Number

Designation

Function

1

T1

Sensor supply 1

2

I1

Analog input 1

3

L-

Reference pole input 1

4

T2

Sensor supply 2

5

I2

Analog input 2

6

L-

Reference pole input 2

7

T3

Sensor supply 3

8

I3

Analog input 3

9

L-

Reference pole input 3

10

T4

Sensor supply 4

11

I4

Analog input 4

12

L-

Reference pole input 4

13

T5

Sensor supply 5

14

I5

Analog input 5

15

L-

Reference pole input 5

16

T6

Sensor supply 6

17

I6

Analog input 6

18

L-

Reference pole input 6

AI

T1 I1 L- T2 I2 L-

41 42 43 44 45 46

Wire Jumpers

Wire Jumpers

I1

T1

L-

AI

L- T2 I2

I3

T3

L-

L- T4 I4

I5

T5

L-

L- T6 I6

I7

T7

L-

L- T8 I8

AI

AI

AI

7 8 9 10 11 12

1 2 3 4 5 6

13 14 15 16 17 18

19 20 21 22 23 24