Use GuardPLC Controller as an Adapter Chapter 19

Configure the PanelView Terminal for EtherNet/IP
Communication

Follow these steps to configure the PanelView terminal.

1. Double-click the Comms. Setup button on the Application

Settings dialog box.

2. When the Communications Setup - Ethernet dialog box opens,

press the Insert key.

3. Choose Generic CIP from the Node Type list.