Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 329

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

329

System Signal Variables Appendix B

AI[xx].Error Code
DI[xx].Error Code

Read
Read

Error mask for analog input channels (1…8)
Error mask for digital input channels (9…32)

0x01

Error in input module

0x02

Measured values invalid

0x04

A/D converter faulty

0x08

Measured value not within the safety accuracy

0x10

Measured value overflow

0x20

Channel not in operation

0x40

Address error of both A/D converters

0x80

Configuration of hysteresis faulty

AI[xx].Value Analog

DI[xx].Value Analog

Read

Read

Analog value of AI channels (1…8) [WORD] from 0…1000
The validity is dependent on the error mask.

Analog value of the DI channels (9…32) [WORD] from 0…3000
The validity is dependent on the error mask.

DI[xx].Value Bool

Read

Digital value of DI channels (9…32) [BOOL] according to hysteresis
The validity is dependent on the error mask.

AI[xx].Hysteresis LOW

Write

Upper limit of the 0-signal voltage range DI[xx].Value Bool

AI[xx].Hysteresis HIGH

Write

Lower limit of the 1-signal voltage range DI[xx].Value Bool

AI[xx].Used
DI[xx].Used

Write
Write

Configuration for indicating utilization of channels 1…8
Configuration for indicating utilization of channels 9…32

I/O Data

Read/Write

Description