System Signal Variables Appendix B
AI[xx].Error Code
DI[xx].Error Code
Read
Read
Error mask for analog input channels (1…8)
Error mask for digital input channels (9…32)
0x01
Error in input module
0x02
Measured values invalid
0x04
A/D converter faulty
0x08
Measured value not within the safety accuracy
0x10
Measured value overflow
0x20
Channel not in operation
0x40
Address error of both A/D converters
0x80
Configuration of hysteresis faulty
AI[xx].Value Analog
DI[xx].Value Analog
Read
Read
Analog value of AI channels (1…8) [WORD] from 0…1000
The validity is dependent on the error mask.
Analog value of the DI channels (9…32) [WORD] from 0…3000
The validity is dependent on the error mask.
DI[xx].Value Bool
Read
Digital value of DI channels (9…32) [BOOL] according to hysteresis
The validity is dependent on the error mask.
AI[xx].Hysteresis LOW
Write
Upper limit of the 0-signal voltage range DI[xx].Value Bool
AI[xx].Hysteresis HIGH
Write
Lower limit of the 1-signal voltage range DI[xx].Value Bool
AI[xx].Used
DI[xx].Used
Write
Write
Configuration for indicating utilization of channels 1…8
Configuration for indicating utilization of channels 9…32
I/O Data
Read/Write
Description
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems