Chapter 22 Communicate with Modbus and Profibus Devices
Connect the Controller to a Modbus Device
Configure the Modbus Serial Port
You must either create a new project or open an existing project
before you can configure Modbus communication. Once the software
opens a project, it automatically displays the Hardware Management
window, from which you configure the Modbus port.
1. Right-click Protocols and choose New>Modbus Slave.
L-
L+
L+
COMM3
ASCII
RS-485
24V DC
COMM2
COMM1
GuardPLC Ethernet
10/100 BaseT
MODBUS
3
(—)
4
(—)
3
(—)
4
(—)
RS-485
Connection
Signal
Function
1
---
---
2
RP
5V, decoupled with diodes
3
RxD/TxD-A
Receive/Transmit data A
4
CNTR-A
Control Signal A
5
DGND
Data reference potential
6
VP
5V, positive pole of supply voltage
7
---
---
8
RxD/TxD-B
Receive/Transmit data B
9
CNTR-B
Control Signal B
IMPORTANT
The Modbus port is RS-485. You must use an electrical
interface device to connect the controller to an RS-232 device.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems