Chapter 22 Communicate with Modbus and Profibus Devices

Connect the Controller to a Modbus Device

Configure the Modbus Serial Port

You must either create a new project or open an existing project
before you can configure Modbus communication. Once the software
opens a project, it automatically displays the Hardware Management
window, from which you configure the Modbus port.

1. Right-click Protocols and choose New>Modbus Slave.

L-

L+

L+

COMM3

ASCII

RS-485

24V DC

COMM2

COMM1

GuardPLC Ethernet

10/100 BaseT

MODBUS

3

(—)

4

(—)

3

(—)

4

(—)

RS-485

Connection

Signal

Function

1

---

---

2

RP

5V, decoupled with diodes

3

RxD/TxD-A

Receive/Transmit data A

4

CNTR-A

Control Signal A

5

DGND

Data reference potential

6

VP

5V, positive pole of supply voltage

7

---

---

8

RxD/TxD-B

Receive/Transmit data B

9

CNTR-B

Control Signal B

IMPORTANT

The Modbus port is RS-485. You must use an electrical
interface device to connect the controller to an RS-232 device.