Use the GuardPLC Controller as a Scanner Chapter 20

For more information on configuring Logix controllers, refer to
Logix5000 Controllers Quick Start, publication

1756-QS001

.

Configure Connections from the GuardPLC Controller to the Logix
Controller

1. In RSNetWorx for EtherNet/IP software, right-click the GuardPLC

scanner controller in the graphic view and choose Scanlist
Configuration.

2. Right-click the target Logix controller in the Scanlist

Configuration dialog box and choose Insert Connection.

3. In this example, the Connection Name is Receive Data From.

4. Enter the name of the producing tag in the Communication

Parameters Value field.

5. Make sure that the Input Size value matches the size of the

producing tag.

6. Once you have set these properties, click the OK button to

apply the changes.

RSNetWorx for EtherNet/IP software displays these changes in
blue under the I/O module entry.

7. Click Save in RSNetWorx for EtherNet/IP software to download

the configuration to the GuardPLC controller.