Configure connections from the guardplc controller, To the logix controller – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 261
![background image](/manuals/579232/261/background.png)
Publication 1753-UM001C-EN-P - March 2010
261
Use the GuardPLC Controller as a Scanner Chapter 20
For more information on configuring Logix controllers, refer to
Logix5000 Controllers Quick Start, publicatio
.
Configure Connections from the GuardPLC Controller to the Logix
Controller
1. In RSNetWorx for EtherNet/IP software, right-click the GuardPLC
scanner controller in the graphic view and choose Scanlist
Configuration.
2. Right-click the target Logix controller in the Scanlist
Configuration dialog box and choose Insert Connection.
3. In this example, the Connection Name is Receive Data From.
4. Enter the name of the producing tag in the Communication
Parameters Value field.
5. Make sure that the Input Size value matches the size of the
producing tag.
6. Once you have set these properties, click the OK button to
apply the changes.
RSNetWorx for EtherNet/IP software displays these changes in
blue under the I/O module entry.
7. Click Save in RSNetWorx for EtherNet/IP software to download
the configuration to the GuardPLC controller.