Read Integers from the Controller and Display Them on the
PanelView Plus Terminal

This example uses input assembly 120 and shows how two integers
can be read by the PanelView Plus terminal. Two INT tags,
fromGuard_INT1 and fromGuard_INT2, were used in the controller as
shown.

The names, tag01 and tag02, in the input assembly window could be
any names unique to the GuardPLC controller. The offsets must be
renumbered by using the New Offsets tab. The order of this offset
determines the order in which these tags appear in the buffer.

The numeric display objects shown below read the two integers from
the GuardPLC controller. Tags N120:0 and N120:1 were used to match
the input assembly used in the GuardPLC controller. The GuardPLC
controller does not use the ‘N’; it is required for FactoryTalk View
software.