Publication 1753-UM001C-EN-P - March 2010

Chapter 7 Wire and Configure the 1753-IB8XOB8 Module

Terminal Connections

See the wire size and terminal torques specifications on page

290

.

Digital outputs are connected to these terminals.

For connection of a load, the reference pole L- of the channel group
must be used. Although L- at terminals 7 and 12 and at terminals 13
and 18 are connected internally to L- on the power supply input, it is
strictly recommended to use 7 and 12 for outputs 1…4 only and 13
and 18 for outputs 5…8 only. EMC testing was performed in this
manner.

Terminal
Number

Designation

Function

4

4-

Negative switching digital output 4 (for increased load or
bi-polar output)

5

8-

Negative switching digital output 8 (for increased load or
bi-polar output)

6

S+

Reference pole for negative switching outputs
(short-circuit protection)

7

L-

Reference pole for positive-switching outputs

8

1

Digital output 1

9

2

Digital output 2

10

3

Digital output 3

11

4

Digital output 4 (for increased load or bi-polar output)

12

L-

Reference pole for positive-switching outputs

13

L-

Reference pole for positive-switching outputs

14

5

Digital output 5

15

6

Digital output 6

16

7

Digital output 7

17

8

Digital output 8 (for increased load or bi-polar output)

18

L-

Reference pole for positive-switching outputs

1

L-

L-

DO

2 3 4

7

8

9

10 11 12

7

8

9

10 11 12

5

L-

L-

DO

6 7 8

13 14 15 16 17 18

13 14 15 16 17 18

1

L-

S+

PO

2 4- 8-

1

2

3

4

5

6

1

2

3

4

5

6

DO