Appendix B System Signal Variables

Digital (Analog) Input Variables for the GuardPLC 1800 Controller

The digital inputs on the GuardPLC 1800 controller are actually analog
inputs with these configurable parameters.

I/O Data

Read/Write

Description

Module.SRS

Read

Slot number (System.Rack.Slot)

Module.Type

Read

Module type

0x00D2

Digital input module (MI24/8 FS:1000) for GuardPLC 1800
controllers

0x0096

Digital input module (MI24/8 FS:2000) for GuardPLC 1800
controllers

Module.Error.Code

Read

Error mask for the module

0x0000

I/O processing may be running with errors

0x0001

No I/O processing (CPU not in RUN)

0x0002

No I/O processing during start-up tests

0x0004

Manufacturing interface running

0x0010

No I/O processing due to incorrect configuration

0x0020

No I/O processing due to exceeded fault rate

0x0040

No I/O processing because configured module is not plugged in

AI.Error Code

Read

Error mask for all digital (analog) inputs

0x0001

Error in input range

0x0008

FTZ test: walking bit of data bus faulty

0x0010

FTZ test: error checking coefficients

0x0020

FTZ test: operating voltages faulty

0x0040

A/D conversion faulty (DRDY_LOW)

0x0080

MEZ test: cross links of MUX faulty

0x0100

MEZ test: walking bit of data bus faulty

0x0200

MEZ test: multiplexer addresses faulty

0x0400

MEZ test: operating voltages faulty

0x0800

MEZ test: measuring system (characteristic) faulty (unipolar)

0x1000

MEZ test: measuring system (final values, zero point) faulty
(unipolar)

0x8000

A/D conversion faulty (DRDY_HIGH)