Publication 1753-UM001C-EN-P - March 2010

211

Introduction to EtherNet/IP Communication Chapter 18

The multistate indicator objects shown below read the two BOOLs
from the GuardPLC controller. Tags B122:0 and B122:1 were used to
match the input assembly used in the GuardPLC controller. The
GuardPLC controller does not use the ‘B’; it is required for FactoryTalk
View software.

B122:0.0 corresponds to the first BOOL tag in the GuardPLC assembly
122. B122:0.8 corresponds to the second BOOL tag in the GuardPLC
assembly 122.

TIP

GuardPLC is a BYTE machine. BOOL tags take up a complete
BYTE in the buffer. That is why .0 and .8 are used in the VIEW
tags to read the first bit from the GuardPLC byte. If a third BOOL
tag was read, the address in the VIEW tag would be B122:1.0.