Use peer-to-peer system signals – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 181

Publication 1753-UM001C-EN-P - March 2010
181
Configure Peer-to-Peer Communication Chapter 17
Use Peer-to-peer System Signals
The status of the peer-to-peer communication as well as some timing
parameters can be evaluated in the user program by means of system
signals. Furthermore, the user program can control how a
peer-to-peer connection is setup.
Input System Signals
These system signals can be used as inputs for the application:
•
Connection State. Using the Connection State system signal of
the Peer-to-Peer Editor, the user program can evaluate the status
of the communication between two controllers. This table shows
the possible values for the Connection State system signal and
the corresponding status.
•
Receive Timeout, in milliseconds, is set by the user.
For more information see
on
Define Peer-to-peer Parameters
on page
.
•
Response Time, in milliseconds, is the actual value of the last
answer message and is identical to RspT last in the P2P status of
the Control Panel.
For more information, see
•
Version indicates the CRC for the peer-to-peer configuration
between two controllers. The CRC must be identical to establish
communication.
Value
Status
Description
0
CLOSED
Communication path is closed. No attempt to connect.
1
TRY_OPEN
Communication path is closed. Attempt to connect.
2
CONNECTED
Communication path is open. No attempt to connect.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems