Chapter 15 Diagnostics

Power Supply and Module Status

I/O Status

While the system is in Run mode, ERR is indicated continuously for
both a module and a counter channel error. Depending on the type of
error, the module may switch off only one counter channel (that is,
the counter transmits the value 0 to the logic, the output has no signal,
but the module continues operation with the remaining counter
channel). If the entire module is switched off, all counter channels are
switched off.

Indicator

Status

Description

RUN

On (green)

The module has the correct operating voltage (24V DC).

Off

The module has no power.

ERR

On (red)

If the system is in Stop mode, one or more of the inputs or
outputs is faulty or the module is faulty.

Use the RSLogix Guard PLUS! software to verify the location
of the fault. If the module is faulty, replace the module
immediately or the safety-related operation of the
GuardPLC 2000 controller is not maintained.

Off

The module is operational.

Indicator

Status

Description

1, 2, 3, 4

On (green)

The corresponding output is energized.

Off

The corresponding output is de-energized.