Use GuardPLC Controller as an Adapter

Introduction

Configure the GuardPLC
Controller as an Adapter

Make sure the GuardPLC controller resource has the EtherNet/IP
protocol added under the Protocols folder in the RSLogix Guard PLUS!
Hardware Management project tree. If it does not, see page

203

for

instructions on adding EtherNet/IP protocol.

Configure the Adapter Input Assembly

Input assemblies contain data that is produced by the GuardPLC
controller and consumed by a scanner.

1. You can use the default input assembly IN_120 or create a new

input assembly by right-clicking EtherNet/IP in the project tree
and choosing New > Input Assembly.

2. Modify the input assembly properties, if desired, by

right-clicking the input assembly and choosing Properties.

Topic

Page

Configure the GuardPLC Controller as an Adapter

215

Open a Class 1 Connection from a Logix Controller to the GuardPLC
Controller

219

Open a Class 3 Connection from a Logix Controller

228

Use a GuardPLC Controller as an Unconnected Adapter

235

Use Unconnected PCCC Messaging from a PLC-5 or SLC 5/05 Controller 235