Wire and Configure the 1753-IB16XOB8 Module Chapter 8

Terminal Connections

See the wire size and terminal torques specifications on page

290

.

Digital inputs are connected to these terminals.

Terminal Number

Designation

Function

33

LS+

Sensor supply for inputs 1… 4
40 mA buffered/1 A unbuffered

34

LS+

Sensor supply for inputs 1…4
40 mA buffered/1 A unbuffered

35

1

Digital input 1

36

2

Digital input 2

37

3

Digital input 3

38

4

Digital input 4

39

L-

Reference pole

40

L-

Reference pole

41

Ground

Shield

42

Ground

Shield

43

LS+

Sensor supply for inputs 5…8
40 mA buffered/1 A unbuffered

44

LS+

Sensor supply for inputs 5…8
40 mA buffered/1 A unbuffered

45

5

Digital input 5

46

6

Digital input 6

47

7

Digital input 7

48

8

Digital input 8

49

L-

Reference pole

50

L-

Reference pole

51

Ground

Shield

52

Ground

Shield

53

LS+

Sensor supply for inputs 9…12
40 mA buffered/1 A unbuffered

54

LS+

Sensor supply for inputs 9…12
40 mA buffered/1 A unbuffered

55

9

Digital input 9

56

10

Digital input 10

57

11

Digital input 11

58

12

Digital input 12

59

L-

Reference pole

60

L-

Reference pole

61

Ground

Shield

62

Ground

Shield

LS+ LS+ 1 2

3

4

L-

L-

33 34 35 36 37 38 39 40 41 42

43 44 45 46 47 48 49 50 51 52

53 54 55 56 57 58 59 60 61 62

63 64 65 66 67 68 69 70 71 72

LS+ LS+ 5 6

7

8

L-

L-

LS+ LS+ 9 10 11 12

L-

L-

LS+ LS+ 13 14 15 16

L-

L-