Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 84

Advertising
background image

84

Publication 1753-UM001C-EN-P - March 2010

Chapter 8 Wire and Configure the 1753-IB16XOB8 Module

supply is read and the supply is switched off if an overcurrent
condition occurs. This supply is protected by a current limiting device.

Follow the closed-circuit principle for external wiring when
connecting sensors. To create a safe state in the event of a fault, the
input signals revert to the de-energized state (0). Although the
external line is not monitored, a wire break is interpreted as a safe
0-signal. Unused inputs must not be terminated.

An EN 61000-4.5 surge impulse can be read as a short-duration HI
signal in some modules. To avoid an error, either:

install shielded input lines to prevent effects of surges in the
system.

implement software filtering in the user program. A signal must
be present for at least two cycles before it is evaluated.

L+ Not Buffered

L+ Not Buffered

L+ Buffered

L+ Buffered

Current

Limiting

40 mA

Current

Limiting

40 mA

Current

Limiting

40 mA

Current

Limiting

40 mA

Current

Limiting

1 A

Current

Limiting

1 A

LS+

LS+

LS+

LS+

LS+

LS+

LS+

LS+

33

34

43

44

53

54

63

64