Monitor for Line Short Line
Break

The Line Short Line Break (LSLB) monitoring measures the impedance
of a load and allows the modules to detect the following faults, when
LSLB monitoring is configured by using the system variable
DO[xx].LSLB:

Short-circuit between DO+ and DO-

Short-circuit DO+ and external L+

Short-circuit between DO+ and external L-

Short-circuit between DO- and external L+

Short-circuit between DO- and external L-

Line break between DO+ and DO-

Line monitoring of the digital outputs is possible only when outputs
are configured for 2-pole operation and both poles DO[xx]- and
DO[xx]+ are wired to a load. A detected line fault is reported in the
system signal DO[xx].+Error Code or DO[xx].-Error Code. See

Appendix B

for information on system signals.

There are two kinds of line monitoring.

Line monitoring for lamp loads and inductive loads

Line monitoring for resistive, capacitive loads

For both types, you must configure a period and time for line
monitoring by using the system signal variables described on page

93

.

Line Monitoring for Lamp and Inductive Loads

For short-circuit detection, a 24V impulse with a duration of 500

μ

s is

switched in the output circuit. Afterwards, a 10V signal is set for the
duration of the monitoring time to detect a line break.

To configure this type of line monitoring:

set a DO.LSLB period and DO.LSLB time.

set the output DO[xx].2-pole signal to 1 (TRUE).

set the output DO[xx].LSLB monitoring signal to 1 (TRUE).

set the output DO[xx].LS monitoring with reduced voltage signal
to 0 (FALSE).

See

Required Signals for Line Monitoring

on page

93

.