Analog Input Module Variables (AB-AI) for GuardPLC 2000
Controller

The GuardPLC 2000 controller supports these analog input
parameters.

I/O Data

Read/Write

Description

AI.Mode

Write

Mode for all channels of the analog input module

0

unipolar (single-ended)

1

differential

AI.State

Read

Error mask for all analog inputs

0x0000

No errors detected

0x0001

Error of the module

0x0008

Within the safety time: data bus walking bit error

0x0010

Within the safety time: coefficient table check error

0x0020

Within the safety time: supply voltages error

0x0040

Error on A/D conversion (DRDY_HIGH)

0x0080

Within the multiple error occurrence time: error in multiplexer
crosslink

0x0100

Within the multiple error occurrence time: data bus walking
bit error

0x0200

Within the multiple error occurrence time: multiplexer address error

0x0400

Within the multiple error occurrence time: supply voltages error

0x0800

Within the multiple error occurrence time: error in characteristic
curve (Unipolar mode)

0x1000

Within the multiple error occurrence time: limit values/zero point
error (Unipolar mode)

0x2000

Within the multiple error occurrence time: error in characteristic
curve (Differential mode)

0x4000

Within the multiple error occurrence time: limit values/zero point
error (Differential mode)

0x8000

Error in A/D conversion (DRDY_LOW)