Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 272
272
Publication 1753-UM001C-EN-P - March 2010
Chapter 21 Communicate with ASCII Devices
For example, this string replies to the master request for the first two
variables from the slave.
Every data field in the message is separated with a slash ( / ). The
slash also counts as a character when counting the total number of
characters in the data string.
If the master request was not received properly at the GuardPLC
controller, the slave response is the following.
This error response is typically sent when more signals are requested
than exist in the ASCII protocol output tab. For example, 10 signals
were dragged to the ASCII output section, but 20 signals were
requested in the command string.
Start Sign
Destination
Source
Function
Code
Start
Address
Number of
Variables
Number of
Characters
Data
End Sign
^
01
15
r
00000
002
0005
4/123
&
TIP
The reply string will have a variable number of characters if
non-BOOL are used. For example, 99 is 2 characters, 100 is 3
characters. There is no leading zero.
Start Sign
Destination
Source
Function
Code
Start
Address
Number of
Variables
Number of
Characters
End Sign
^
01
15
E
00000
000
0000
&