Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 321

Publication 1753-UM001C-EN-P - March 2010
321
System Signal Variables Appendix B
DO[xx].+Error Code
(1)
DO[xx].-Error Code
Read
Error code of digital outputs DO+
Error code of digital outputs DO-
0x0001
Error in the digital output module
0x0002
Output switched off due to overload
0x0004
Error reading back the activation of digital outputs
0x0008
Error reading back status of the digital outputs
0x0010
Short-circuit
0x0020
Channel is switched off due to an error in the corresponding DO
channel
0x0040
Zener diode at the output is not alloyed
0x0080
Line break
0x0100
MEZ test of the output switches in the DO+ line caused an error
0x0200
MEZ test of the output switches in the DO- line caused an error
0x0400
MEZ test of the L- test switch caused an error
0x0800
External L+ supply at DO+
DO.LSLB period
(2)
Write
Period during which line monitoring is carried out.
Values in one second increments from 1…100 s.
DO.LSLB time
Write
Time for Line Short Line Break (LSLB) monitoring.
Values in one millisecond increments from 0 …50 ms. The default is 0 ms.
DO[xx].2-pole
Write
Configures the module for 2-pole operation
0
1-pole operation
1
2-pole operation
DO[xx].+Value
Write
Output value for DO channels (DO+)
1-pole (Value:0 or 1)
2-pole, identical to DO- (Value: 0 or 1)
DO[xx].-Value
Write
Output value for DO channels (DO-)
1-pole (Value:0 or 1)
2-pole, identical to DO+ (Value: 0 or 1
DO[xx].LSLB monitoring
Write
Configures line control
0
no LSLB (line control)
1
set for LSLB (line control)
DO[xx]LS monitoring with
reduced voltage
Write
Configures line control with reduced voltage
0
normal signal voltage level
1
reduced signal voltage level
DO[xx][xx].in pairs
Write
Configures line control with channel pairs
Pair 1
channel 1 [01] and channel 2 [02
Pair 2
channel 3 [03] and channel 4 [04
Pair 3
channel 5 [05] and channel 6 [06
Pair 4
channel 7 [07] and channel 8 [08]
(1) xx = affected output channel of the controller or module.
(2) LSLB = Line Short Line Break
I/O Data
Read/Write
Description
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems