Chapter 13 Controller Configuration and Modes of Operation
Routine Modes
The controller runs only one routine. The following table and
flowchart summarize the routine modes.
Mode
Description
Run_Run
The controller is in the Run mode.
•
The routine is executed cyclically by the controller.
•
Input data are processed in the routine.
•
Output data of the routine are operated.
Run_Freeze
The controller is in the Run mode.
•
The routine is not executed.
•
No input data are processed.
•
No output data of the routine are operated.
Stop
The controller is in the Stop mode.
•
The routine is no longer being executed.
•
All outputs have been reset.
Failure_Stop
The controller is in the Stop mode.
•
The routine was stopped due an error.
•
All outputs are reset.
•
The hardware watchdog is not triggered.
•
To recover from Failure_Stop, a restart of the controller is necessary. A restart can be
initiated only via RSLogix Guard PLUS! software. See
Test Mode (single step)
The controller is in Run mode.
•
The routine is triggered manually.
•
I/O data are processed.
IMPORTANT: Test Mode is not permitted for safe operation.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems