Safety-related Digital
Outputs

The module has 8 digital output pairs, each with a positive- and
negative-switching output. The digital outputs are not electrically
isolated.

An output is in the safe state when it is de-energized. Therefore,
outputs are switched off when a fault that affects the safety control of
those outputs occurs.

If an overload occurs, the affected output is switched off. If the total
current exceeds 9 A, all eight outputs are switched off. When the
overload is eliminated, the outputs are activated again according to
their current software-driven state.

Configuration

The digital outputs can be configured three ways.

1-pole switch (no line monitoring)

2-pole switch (with or without line monitoring)

3-pole switch (2-pole with common reference)

63

LS+

Sensor supply for inputs 13…16
40 mA buffered/1 A unbuffered

64

LS+

Sensor supply for inputs 13…16
40 mA buffered/1 A unbuffered

65

13

Digital input 13

66

14

Digital input 14

67

15

Digital input 15

68

16

Digital input 16

69

L-

Reference pole

70

L-

Reference pole

71

Ground

Shield

72

Ground

Shield

Terminal Number

Designation

Function