Communication status indicators – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 144

Advertising
background image

144

Publication 1753-UM001C-EN-P - March 2010

Chapter 15 Diagnostics

Communication Status Indicators

Status indicators on the controllers and I/O modules display
communication status information.

Safety-related GuardPLC Ethernet Communication

Communication via the GuardPLC Ethernet network is indicated via
two small status indicators integrated into each RJ-45 connector
socket.

Non-safety-related Communication

Active communication via the serial ports, COMM1 and COMM3, is
indicated by a status indicator located above the port.

PROGress

On

The upload of a new controller configuration is in progress.

Flashing

The upload of a new operating system into the Flash ROM is in progress.

Off

No upload of controller configuration or operating system in progress.

FORCE

On

The controller is executing a routine (Run) and Force mode is activated by the user.

Flashing

The controller is in Stop, but Forcing has been initiated and will be activated when the controller is
started.

Off

Forcing is OFF.

FAULT

On

The routine (logic) has caused an error.

The controller configuration is faulty.

The upload of a new operating system was not successful and the operating system is corrupted.

Flashing

An error has occurred during a Flash ROM write cycle.

One or more I/O errors have occurred.

Off

None of the above errors has occurred.

OSL

Flashing

Emergency Operating System Loader is active.

BL

Flashing

Boot Loader unable to load operating system or unable to start COMM operating system loader.

Indicator

State

Description

Indicator

State

Description

Green

On

Full duplex operation

Flashing

Collision

Off

Half duplex operation, no collision

Yellow

On

Connection established

Flashing

Interface activity