Chapter 2 Installation

Communication
Connections

Connections for safety and non-safety related communication for
GuardPLC controllers and distributed I/O modules are described in
the following sections.

GuardPLC 1200 Controller

The GuardPLC 1200 controller has an ASCII serial port for
non-safety-related communication and an Ethernet port for
safety-related communication.

Connect the ASCII port to any RS-232 device that has the capability to
send ASCII command strings to the controller. The controller replies
with a data variable string. See

Chapter 21

for more information on

ASCII communication

Use this illustration to connect the ASCII and Ethernet ports.

The pin assignment of the ASCII Serial port is shown below.

PLC

1200

ASCII
Serial Port
(Use 1761-CBL-PM02
Series C Cable)

Ethernet Port
(On Bottom of Controller)

Port for
Factory
Use
Only

Ethernet Dongle

4

5

7

1

2

8

6

3

Pin

Function

1

24V DC

2

ground (GND)

3

request to send (RTS)

4

received data (RxD)

5

received line signal detector (DCD)

6

clear to send (CTS)

7

transmitted data (TxD)

8

ground (GND)

9

not applicable