Connect to a guardplc 1600 or 1800 controller – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 266

Advertising
background image

266

Publication 1753-UM001C-EN-P - March 2010

Chapter 21 Communicate with ASCII Devices

D-shell connector. This mini-DIN connector is not commercially
available, so you cannot make this cable.

The pin assignment of the ASCII Serial port is shown below.

Connect to a GuardPLC 1600 or 1800 Controller

The ASCII COMM3 port location and connector pin assignment are
shown below.

Connection

Signal

Function

1

---

---

2

RP

5V, decoupled with diodes

3

RxD/TxD-A

Receive/Transmit data A

4

CNTR-A

Control Signal A

5

DGND

Data reference potential

6

VP

5V, positive pole of supply voltage

7

---

---

8

RxD/TxD-B

Receive/Transmit data B

9

CNTR-B

Control Signal B

IMPORTANT

The ASCII port is RS-485. You must use an electrical interface
device to connect the controller to an RS-232 device.

4

5

7

1

2

8

6

3

Pin

Function

1

24V DC

2

ground (GND)

3

request to send (RTS)

4

received data (RxD)

5

received line signal detector (DCD)

6

clear to send (CTS)

7

transmitted data (TxD)

8

ground (GND)

9

not applicable

L-

L+

L+

COMM3

ASCII

RS-485

24V DC

COMM2

COMM1

GuardPLC Ethernet

10/100 BaseT

PROFIBUS

3

(—)

4

(—)

3

(—)

4

(—)