Connect to a guardplc 1600 or 1800 controller – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 266

266
Publication 1753-UM001C-EN-P - March 2010
Chapter 21 Communicate with ASCII Devices
D-shell connector. This mini-DIN connector is not commercially
available, so you cannot make this cable.
The pin assignment of the ASCII Serial port is shown below.
Connect to a GuardPLC 1600 or 1800 Controller
The ASCII COMM3 port location and connector pin assignment are
shown below.
Connection
Signal
Function
1
---
---
2
RP
5V, decoupled with diodes
3
RxD/TxD-A
Receive/Transmit data A
4
CNTR-A
Control Signal A
5
DGND
Data reference potential
6
VP
5V, positive pole of supply voltage
7
---
---
8
RxD/TxD-B
Receive/Transmit data B
9
CNTR-B
Control Signal B
IMPORTANT
The ASCII port is RS-485. You must use an electrical interface
device to connect the controller to an RS-232 device.
4
5
7
1
2
8
6
3
Pin
Function
1
24V DC
2
ground (GND)
3
request to send (RTS)
4
received data (RxD)
5
received line signal detector (DCD)
6
clear to send (CTS)
7
transmitted data (TxD)
8
ground (GND)
9
not applicable
L-
L+
L+
COMM3
ASCII
RS-485
24V DC
COMM2
COMM1
GuardPLC Ethernet
10/100 BaseT
PROFIBUS
3
(—)
4
(—)
3
(—)
4
(—)
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems