Publication 1753-UM001C-EN-P - March 2010

89

Wire and Configure the 1753-IB16XOB8 Module Chapter 8

3-pole Connection With Line Monitoring

Two 2-pole channels can support dual-channel devices with only a
single reference connection. If line monitoring is required, the
channels must be configured in pairs, using the system parameter
DO[xx][xx].in pairs. There are four pairs allowed: channels 1 and 2,
channels 3 and 4, channels 5 and 6, and channels 7 and 8.

Line monitoring is accomplished by switching off one channel while
the second channel is tested for wiring faults.

A detected line fault is reported by the module’s error codes. See

Appendix B

for error code information.

IMPORTANT

Inductive loads must be connected with a protection diode on
the load for 3-pole connections.

1753-IB16XOB8

Load

(drive, valve)

3-pole Configuration