69

Publication 1753-UM001C-EN-P - March 2010

69

Chapter

6

Wire 1753-IB16, 1753-OB16, and
1753-IB20XOB8 Modules

Introduction

Safety-related Digital
Inputs

The status of digital inputs is indicated via status indicators when the
module is in Run mode.

Follow the closed-circuit principle for external wiring when
connecting sensors. To create a safe state in the event of a fault, the
input signals revert to the de-energized state (0). The external line is
not monitored, but a wire break is interpreted as a safe (0) signal.

The GuardPLC 1600 and GuardPLC 1800 controllers provide power to
input devices through their LS+ terminals. However, input devices
with their own dedicated power supply can also be connected instead
of contacts. The reference pole (L-) of the power supply must then be
connected to the reference pole (L-) of the appropriate GuardPLC
input group. See the wiring diagrams in

Appendix C

for examples.

In general, the LS+ terminals, not L+ on the power supply connection,
should be used to supply voltage for safety inputs. Each LS+ features
individual short-circuit and EMC protection. Due to current limitations,
use LS+ for only the safety inputs on the same terminal plug.

An EN 61000-4.5 surge impulse can be read as a short-duration HI
signal in some modules. To avoid an error, either:

install shielded input lines to prevent effects of surges in the
system.

implement software filtering in the user program. A signal must
be present for at least two cycles before it is evaluated.