Diagnostics Chapter 15

GuardPLC 2000 Controller
Status Indicators

The GuardPLC 2000 controller has status indicators for:

module, both the program and the communication.

controller and the system hardware.

routine.

Ethernet communication to the programming terminal.

Controller Indicators

Indicator Status

Description

RUN

On

This is the normal status of the controller (Run or Stop mode).

The controller carries out communication and performs software
tests.

Flashing

Downloading an Operating System

Off

The controller is in Failure_Stop (see ERR below), or there is no
power supply.

ERR

On

The controller is in the Failure_Stop state and the execution of
the routine is halted. All system outputs will be reset and the
controller ceases all hardware and software tests.

The operating system loader has found a flash error (FAULT is
blinking).

Flashing

The boot loader has found an error in the operating system in the
flash (if all other indicators are ON); the download of a new
operating system is awaited.

Off

No errors are detected.

10/100BaseT

Tx COL

FORCE

PROG FAULT

RUN STOP

RUN ERR