Digital output parameters for 1753-ib16xob8, Modules – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 320

Advertising
background image

320

Publication 1753-UM001C-EN-P - March 2010

Appendix B System Signal Variables

Digital Output Parameters for 1753-IB16XOB8 Modules

In addition to the output parameters in the table on page

318

, the

GuardPLC 1753-IB16XOB8 module features these digital output
parameters.

DO2[xx].2 Pole used

Write

Configures the channel for 2 pole operation.

0

channel DO2[xx] is not used for 2-pole operation.

1

channel DO2[01] is used for 2-pole operation with channel
DO1[04], or
channel DO2[02] is used for 2-pole operation with channel
DO1[08]

Switch-on delay

Write

Sets switch-on delay for 2-pole tests, due to lamp load, inductive and
capacitive load

(1) xx = affected output channel of the controller or module.

I/O Data

Read/
Write

Description

L+ Switching Outputs

L- Switching Outputs

I/O Data

Read/Write

Description

DO.Error Code

Read

Error mask for all digital outputs

0x0001

Error in digital output range

0x0002

MEZ test of safety shutdown failed

0x0004

MEZ test, auxiliary supply failed

0x0008

FTZ test of test pattern failed

0x0010

MEZ test of test pattern of the output switch failed

0x0020

MEZ test of test pattern of the output switch (disconnection test of
outputs) failed

0x0040

MEZ test, active disconnection via watchdog failed

0x0080

FTZ test of the period monitoring causes an error.

0x0100

FTZ read back of the period monitoring causes an error

0x0200

All outputs switched off, total current exceeded

0x0400

FTZ test: 1. Temperature threshold exceeded

0x0800

FTZ test: 2. Temperature threshold exceeded

0x1000

FTZ test: Monitoring of auxiliary supply 1: Undervoltage

0x2000

FTZ test: Monitoring of auxiliary supply 2: Undervoltage

0x4000

Flip-flop of the supply monitoring (18V) causes undervoltage

0x8000

MEZ test of the period monitoring causes an error