Safety-related digital outputs, Terminal connections surge on digital inputs, Terminal connections – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 78: Surge on digital inputs

Advertising
background image

78

Publication 1753-UM001C-EN-P - March 2010

Chapter 7 Wire and Configure the 1753-IB8XOB8 Module

Terminal Connections

See the wire size and terminal torques specifications on page

290

.

Digital inputs are connected to these terminals.

Surge on Digital Inputs

An EN 61000-4.5 surge impulse can be read as a short-duration HI
signal in some modules. To avoid an error, either:

install shielded input lines to prevent effects of surges in the
system.

implement software filtering in the user program. A signal must
be present for at least two cycles before it is evaluated.

Safety-related Digital
Outputs

The module has 8 positive-switching digital outputs that switch
+24V DC and two negative-switching digital outputs that switch
24V COM. Their status is indicated via status indicators.

The positive and negative-switching digital outputs can be connected
in a one-pole or two-pole manner.

If configured for one-pole operation, use the reference pole L- for the
positive-switching outputs and reference pole S+ for the

Terminal Number

Designation

Function

19

LS+

Sensor supply for inputs 1… 4

20

1

Digital input 1

21

2

Digital input 2

22

3

Digital input 3

23

4

Digital input 4

24

L-

Reference pole

25

LS+

Sensor supply for inputs 5 …8

26

5

Digital input 5

27

6

Digital input 6

28

7

Digital input 7

29

8

Digital input 8

30

L-

Reference pole

1

LS+

L-

DI

2 3 4

19 20 21 22 23 24

19 20 21 22 23 24

LS+ 5

L-

DI

6 7 8

25 26 27 28 29 30

25 26 27 28 29 30

Advertising