Chapter 14 Use the Control Panel to Monitor Status

Resource State Tab

This field

Displays

CPU State

The current state of the controller.

Possible states are Init, Run, Stop/Valid_Configuration, Stop/Invalid_Configuration, and
Failure_Stop. See

Controller Modes

on page

113

.

COM State

State of the communication portion of the controller.

Possible states are Run, Stop, and OS_Loading.

Program Name

The routine name.

The name assigned by the user to the routine. The default name is ‘Routine.’

Program State

The current state of the routine.

Possible states are Run, Stop, Freeze, and Failure_Stop. See

Routine Modes

on page

120

.

Faulty I/O Modules

The number of faulty I/O modules, when the controller is in Run.

Force State

The force status.

0 – forcing is disabled
1 – ready for forcing (the controller is in stop but is set for forcing)
2 – forcing is active

Remaining Force Time [s]

The remaining force time in seconds.