Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 310

Advertising
background image

310

Publication 1753-UM001C-EN-P - March 2010

Appendix B System Signal Variables

AI[0x].State

(1)

Read

Error mask for analog input channels

0x00

No error detected

0x01

Error in analog input channel

0x02

Invalid measurement values

0x04

A/D converters faulty

0x08

Measurement values are not within the safety accuracy

0x10

Measurement value overflow

0x20

Channel not in use

0x40

Addressing error of the two A/D converters

AI[0x].Used

Write

Configuration of analog input channel

0

not used

1

used

AI[0x].Value

(1)

Read

Analog value of input channel (WORD)
-10V…10V = -1000…1000

Board.SRS

Read

System.Rack.Slot

Board.Type

Read

Module type

0xFD02

analog input module for GuardPLC 2000 controller

0xFFFF

missing module in GuardPLC 2000 chassis

Board.State

Read

Error mask for the module

0x000

I/O processing may be running with errors

0x001

No I/O processing (CPU not in RUN)

0x002

No I/O processing during start-up tests

0x004

Manufacturing interface running

0x010

No I/O processing due to faulty parameterization

0x020

No I/O processing due to exceeded fault rate

0x040

No I/O processing because configured module is not plugged in

(1) 0x = input channel 01…08.

I/O Data

Read/Write

Description