Terminal connections, Guardplc 2000 chassis, Terminals accommodate wire sizes up to 1.5 mm – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 47: 16 awg) for input/output wiring and up to 2.5 mm, 14 awg) for voltage supply connections

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

47

General Wiring Considerations Chapter 3

GuardPLC 1600 and GuardPLC 1800 Controllers and Distributed I/O

The I/O module is functionally grounded through its DIN rail
connection. A protective earth ground connection is required and is
provided by a separate grounding screw, located on the upper left of
the housing and marked with the grounding symbol

.

GuardPLC 2000 Chassis

Ground the GuardPLC 2000 chassis and cables by using the grounding
screw located on the left side of the grounding grill. Ground the
chassis via the grounding grill.

Terminal Connections

Terminals accommodate wire sizes up to 1.5 mm

2

(16 AWG) for

input/output wiring and up to 2.5 mm

2

(14 AWG) for voltage supply

connections.

ATTENTION

This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example,
aluminum and plastic) that can corrode, oxidize, or are poor
conductors, can result in improper or intermittent grounding.