High-Speed Counters

Introduction

This chapter covers using counters in these systems:

GuardPLC 1200 controllers

GuardPLC 1800 controllers

GuardPLC 2000 controllers using a 1755-HSC module

Counter/Decoder Modes

The counters can be used in these operating modes:

Counter mode

Decoder mode

The two counters can be used in different modes at the same time.

Counter Mode

Counter mode is used for counting pulses at speeds up to 1 MHz on
the GuardPLC 2000 controllers and 100 kHz on the GuardPLC 1200
and 1800 controllers.

Follow these guidelines when using counters in a GuardPLC system:

The 5V signal must be between 4.5V and 5.5V, while the 24V
signal must be between 13V and 26.4V.

The steepness of the falling edge must be at least 1V per

μ

s.

The low and high signal times must be at least 5

μ

s for the

GuardPLC 1200 controller (duty cycle 50% at 100 kHz) and
0.5

μ

s for the GuardPLC 2000 controller (duty cycle 50% at

1 MHz).

Shield the cable against noise.