Digital output parameters for 1753-ib8xob8, Modules – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 319

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

319

System Signal Variables Appendix B

Digital Output Parameters for 1753-IB8XOB8 Modules

In addition to the output parameters in the table on page

318

, the

GuardPLC 1753-IB8XOB8 module features these digital output
parameters.

I/O Data

Read/
Write

Description

L+ Switching Outputs

L- Switching Outputs

DO1.Error Code

DO2.Error Code

Read

Error mask for all digital outputs

0x0001

Error in digital output range

0x0002

MEZ test of safety shutdown failed

0x0004

MEZ test, auxiliary supply failed

0x0008

FTZ test of test pattern failed

0x0010

MEZ test of test pattern of the output switch failed

0x0020

MEZ test of test pattern of the output switch (disconnection test
of outputs) failed

0x0040

MEZ test, active disconnection via watchdog failed

0x0200

All outputs switched off, total current exceeded

0x0400

FTZ test: 1. Temperature threshold exceeded

0x0800

FTZ test: 2. Temperature threshold exceeded

0x1000

FTZ test: Monitoring of auxiliary supply 1: Undervoltage

DO1[xx].Error Code

(1)

DO2[xx].Error Code

(1)

Read

Error mask of all digital output channels

0x01

Error in digital output module

0x02

Output switched off due to overload

0x04

Error when reading back the activation of the digital outputs

0x08

Error when reading back the status of the digital outputs

0x40

external short-circuit or short-circuit of EMC protection yield to
an error

0x80

channel is switched off due to an error in the corresponding DO
channel

DO1[xx].Value

DO2[xx].Value

Write

Output value of the digital output channels

0

The output is not set, no current

1

The output is set