Publication 1753-UM001C-EN-P - March 2010

197

Configure Peer-to-Peer Communication Chapter 17

Reconfigure Receive Timeout

1. Set the new ReceiveTMO to: 2 x ResponseTime.

2. The Worst Case Reaction Time is optimized and displayed in the

Peer-to-Peer Editor (see above).

3. Compile the project.

4. Download the routines in the controllers again.

5. Start and test your application.