Chapter 18 Introduction to EtherNet/IP Communication
These momentary pushbutton objects write the two integers to the
GuardPLC controller. Tags N123:0 and N123:1 were used to match the
output assembly used in the GuardPLC controller. The GuardPLC
controller does not use the ‘N’; it is required for FactoryTalk View
software.
N123:0 corresponds to the first two BOOL tags in the GuardPLC
assembly 123. The first tag changes between 0 and 1; the second is
the dummy tag. N123:1 corresponds to the next two BOOL tags in the
GuardPLC assembly 123.
Advertising
This manual is related to the following products:
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems