Chapter 15 Diagnostics

Routine Indicators

Ethernet Communication Indicators

Indicator

Status

Description

RUN

On

The routine is in Run or Freeze.

Off

The routine is in Failure_Stop.

STOP

On

The routine is in Stop or Failure_Stop.

PROG

On

The download of a new controller configuration is in progress.

Flashing

The download of a new operating system into the flash ROM is in
progress.

Off

No download of controller configuration or operating system is in
progress.

FAULT

On

The routine (user program) has caused an error.

The controller configuration is faulty.

The download of a new operating system was not successful and
the operating system is corrupted.

Flashing

An error has occurred during a flash ROM write cycle of the
operating system.

At least one I/O module error is present.

Off

No errors have been detected.

FORCE

On

The controller is executing a routine (RUN) and one or more
inputs and/or outputs may be forced by the user.

Flashing

The controller is in Stop mode, but one or more inputs and/or
outputs have been prepared for forcing and will be activated as
soon as the controller is started.

Off

No inputs and/or outputs are forced or are prepared to be forced.

Indicator

Status

Description

Tx

On

Data is transmitting via the Ethernet network by the
communication processor.

COL

On

A collision on the Ethernet network is detected.

10/100BaseT

Tx COL

FORCE

PROG FAULT

RUN STOP

RUN ERR

1755-

L1

Tx COL

10/100 Base T