Wire the GuardPLC 2000 Controller and I/O Chapter 5

There are 4 reference poles for the 8 outputs. A pair of outputs share
a reference pole as shown below.

Each group of 2 outputs is electrically isolated from the others.

These outputs

Share these Reference Poles

1 and 2

O1- and O2-

3 and 4

O3- and O4-

5 and 6

O5- and O6-

7 and 8

O7- and O8-

IMPORTANT

If an unused channel is defined as a current output (software
configuration set to current output), the output channel has to
be short-circuited. Place jumpers into these outputs and tighten
the screws.

IMPORTANT

If an unused channel is defined as a voltage output (software
configuration set to voltage output), the unused outputs must be
left open. Short-circuiting a unused voltage output may cause
damage to the output.

Terminal Number

Designation

Function

1

O1+

Analog output 1

2

O1-

Group 1 reference pole

3

O2+

Analog output 2

4

O2-

Group 1 reference pole

5

O3+

Analog output 3

6

O3-

Group 2 reference pole

7

O4+

Analog output 4

8

O4-

Group 2 reference pole

9

shield connection

signal ground

10

O5+

Analog output 5

11

O5-

Group 3 reference pole

12

O6+

Analog output 6

13

O6-

Group 3 reference pole

14

O7+

Analog output 7

15

O7-

Group 4 reference pole

16

O8+

Analog output 8

17

O8-

Group 4 reference pole

18

shield connection

signal ground

RUN ERR

1755-

OF8

1
2
3
4
5
6
7
8
9

O1-

O2+

O2-

O3+

O4+

10
11
12
13
14
15
16
17
18

O1+

O3-

O4-

O5-

O6+

O6-

O7+

O8+

O5+

O7-

O8-