Communicate with ASCII Devices Chapter 21

For example, this string requests the first two variables from the slave.

ASCII Slave - Controller Response

If the controller receives a request from an ASCII master, it responds
in this format (each character is one byte).

Start Sign

Destination

Source

Function Code

Start Address

Number of
Variables

End Sign

^

15

01

R

00000

002

&

Start Sign

Destination

Source

Function
Code

Start
Address

Number of
Variables

Number of
Characters

Data

End Sign

1 char

2 char

2 char

1 char

5 char

3 char

4 char

maximum
10000 char

1 char

Component

Description

Start Sign

identifies the start of a message
^ character

Destination

unique master address (requester)
01…99

Source

unique slave address (GuardPLC controller)
01…99

Function Code

r character identifies data sent by slave
E identifies error with master request

Start Address

data start address for characters to read (offset)
00000…65535

Number of Variables

number of variables to read and send back to master
000…999

Number of Characters

number of characters in the data string (This includes
the “/” delimiter but not the “&” termination character.)
0000…9999

Data

data characters

End Sign

needed to recognize the end of a message
& character