Page 262
262
Publication 1753-UM001C-EN-P - March 2010
Chapter 20 Use the GuardPLC Controller as a Scanner
Save the Connection
Configuration in the
GuardPLC Controller
Up to this point, only the configuration has been downloaded to the
GuardPLC controller. The offline project currently contains only the
assigned signal connections.
Once the connection configuration is saved with the RSLogix Guard
PLUS! project, you can switch to other projects, reprogram the
GuardPLC controller, and be sure that when the configuration is
loaded back to the GuardPLC controller, it will use this RSNetWorx
configuration to reestablish connections.
Follow these steps to upload the online configuration to your offline
project.
1. Open the Control Panel in RSLogix Guard PLUS! Hardware
Management by choosing Control Panel from the Online menu.
2. Click the EIP tab.
3. Press the FS Upload button to upload the connection
configuration and add it to the project configuration.
An RSNetWorx Configuration sub-branch will be added to the
project tree under the EtherNet/IP Scanner branch.
4. Right-click the controller Resource in the project tree and choose
Code Generation to compile the configuration code.