Chapter 20 Use the GuardPLC Controller as a Scanner

7. Once you have set these properties, click the OK button to

apply the changes.

RSNetWorx for EtherNet/IP software displays these changes in
blue under the I/O module entry.

8. Repeat steps

5

7

for all target I/O modules and press the Save

button to download the connection configuration to the
GuardPLC controller.

Input Size

Input size is the length of the data sent from the I/O module (target) to the GuardPLC controller (scanner). The value in
this field is predetermined by the module type and cannot be changed.

Output Size

Output size is the length of the data sent from the GuardPLC controller (scanner) to the I/O module (target). The value in
this field is predetermined by the module type and cannot be changed.

Configuration
Size

Configuration Size is the size of the configuration data sent with the connection establishment request.

Input Address

The Input Address is the offset in words of the GuardPLC input scanner assembly where the GuardPLC controller will
store the input data from the target device. Enter the Input Address.

Output
Address

The Output Address is the offset in words of the GuardPLC controller’s scanner output assembly buffer where the
GuardPLC controller will store its data before sending it to the target device, in this case the FLEX I/O module.

Property

Description

TIP

If you get a ‘Type’ error and the save procedure is
aborted, it is most likely a data type error with the
signals in the RSLogix Guard PLUS! software scanner
configuration. Make sure that you have not tried to cross
a data type boundary or that you have not used a module
with an odd number of bytes with INT or WORD data
types.